| 7 |
PROBLEM: |
|
|
NOT ENOUGH WATER TO FIXTURE |
|
|
|
|
|
CAUSE: |
|
|
A) WRONG FLUSH VOLUME REGULATOR
INSTALLED IN FLEX TUBE DIAPHRAGM KIT |
|
|
B) WRONG OPTIMA PLUS MODEL INSTALLED;
I.E. 1.0 GPF URINAL INSTALLED ON 3.5 GPF CLOSET FIXTURE. |
|
|
C) ENLARGED BYPASS IN DIAPHRAGM |
|
|
D) CONTROL STOP NOT
ADJUSTED PROPERLY |
|
|
E) INADEQUATE VOLUME OR PRESSURE
AT SUPPLY |
|
|
|
|
|
SOLUTION: |
|
|
A) INSTALL THE CORRECT REGULATOR |
|
|
B) REPLACE WITH PROPER OPTIMA
PLUS MODEL |
|
|
C) REPLACE FLEX TUBE DIAPHRAGM |
|
|
D) READJUST CONTROL STOP |
|
|
E) INCREASE WATER
PRESSURE OR SUPPLY (FLOW) TO VALVE |
|
|
| 8 |
PROBLEM: |
|
|
TOO MUCH WATER TO FIXTURE |
|
|
|
|
|
CAUSE: |
|
|
A) WRONG FLUSH VOLUME
REGULATOR INSTALLED IN FLEX TUBE DIAPHRAGM KIT |
|
|
B) CONTROL STOP NOT
ADJUSTED PROPERLY. |
|
|
C) WRONG OPTIMA PLUS
MODEL INSTALLED; I.E. 3.0 GPF MODEL INSTALLED ON 1.0 OR 1.5
GPF URINAL FIXTURE. |
|
|
D) DIRT IN DIAPHRAGM
BYPASS |
|
|
|
|
|
SOLUTION: |
|
|
A) INSTALL THE CORRECT
REGULATOR |
|
|
B) READJUST CONTROL
STOP |
|
|
C) REPLACE WITH PROPER
OPTIMA PLUS MODEL |
|
|
D) CLEAN UNDER RUNNING
WATER OR REPLACE FLEX TUBE DIAPHRAGM |
|
|
|
|
|
|
|
BATTERY REPLACEMENT
|
| |
|
|
| |
When
required, replace batteries with four (4) Alkaline Type
AA Batteries. Note: Water does not have to be turned off
to replace batteries. Loosen the two (2) Screws on top
of unit. Remove the complete Cover Aseembly. Lift the Sensor
Module from its Plate. Unplug the Electrical Connector
from Battery Compartment Cover. Loosen the Retaining Screw
on Battery Compartment Cover. Install four (4) Alkaline
Type AA Batteries exactly is illustrated below. |
|
| |
|
|
| |
Install
Battery Compartment Cover and secure with Retaining Screw.
Make certain that Battery Compartment Cover is fully
compressed against Gasket to provide a seal. Do not overtighten.
Plug the Electrical Connector into the Battery Compartment
Cover. Reinstall the Sensor Module onto the Plate. Reinstall
the complete Cover Assembly onto the Plate. Tighten the
two (2) Screws on top of the unit.
|
|
|
| |
|
|
|
|
|
|
|
CARE & CLEANING INSTRUCTIONS
|
| |
DO
NOT use abrasive or chemical cleaners to clean Flushometers,
they may dull the luster and attack the chrome or special
decorative finishes. Use ONLY soap and water, then
wipe dry with clean cloth or towel. While cleaning
the bathroom tile, the Flushometer should be protected
from any splattering of cleaner. Acids and cleaning
fluids can discolor or remove chrome plating. |
|
|
|
|
|
|
|
|
|
|
|
FOR BREAKDOWNS AND TROUBLESHOOTING
GUIDES
FOR OTHER SLOAN FLUSHOMETERS, CLICK HERE
|
|
|
|
|