1 |
PROBLEM: |
|
Faucet
does not function |
|
|
CAUSES: |
|
A) Adhesive
packaging label affixed over sensor eye. |
|
B) "Permanent
Off" activated |
|
|
SOLUTIONS: |
|
A) Remove
adhesive label from sensor eye. |
|
B) Press
button on Faucet throat one time |
|
|
| |
|
|
2 |
PROBLEM: |
|
|
Faucet
delivers water in an uncontrolled manner |
|
|
CAUSES: |
|
A) Faucet
is defective. |
|
|
SOLUTION: |
|
A) Replace
Sensor (part # 80771) and/or Solenoid (part
# 54826.) Call Equiparts at 800-442-6622 to order. |
|
|
| |
|
|
3 |
PROBLEM: |
|
|
Faucet
does not deliver any water when sensor is activated. |
|
|
INDICATOR: |
|
|
Solenoid
valve produces an audible "CLICK". |
|
|
CAUSES: |
|
|
A) Water
supply stop(s) closed. |
|
B) Water
supply stop strainer(s) clogged. |
|
|
SOLUTIONS: |
|
|
A) Open
the Water Supply Stop(s). |
|
B) Clean
water supply stop strainer(s) or replace strainer(s) if required.
Order part #
80759 from Equiparts
by calling 800-442-6622. |
|
|
INDICATOR: |
|
|
Solenoid
valve does NOT produce an audible "CLICK". |
|
|
CAUSES: |
|
|
A) Battery
low. |
|
|
SOLUTIONS: |
|
|
A) Replace
battery. Order part # 80775 from Equiparts by calling 800-442-6622. |
|
|
|
4 |
PROBLEM: |
|
|
Faucet
delivers only a slow flow or dribble when sensor is activated |
|
|
CAUSE: |
|
|
A) Water
supply stops(s) partially closed. |
|
B) Water
supply stop strainer(s) clogged. |
|
C) Aerator
is clogged. |
|
D) Faucet
is defective. |
|
|
SOLUTIONS: |
|
A) Completely
open water supply stop(s). |
|
B) Remove,
clean, and reinstall water supply stop strainer(s). Replace
strainer if required. Order part # 80759 from Equiparts
by calling 800-442-6622. |
|
C) Remove,
clean, and reinstall aerator. Replace aerator if required.
See diagram above for proper replacement (Item #3.) |
|
D) Contact
Equiparts for further troubleshooting advice at 800-442-6622. |
|
|
|
5 |
PROBLEM: |
|
|
Faucet
does not stop delivering water or continues to drip after
user is no longer detected. |
|
|
CAUSES: |
|
|
A) Solenoid
Valve requires replacement. |
|
|
SOLUTION: |
|
A) Replace
Solenoid Valve. Order part # 58426 from Equiparts
by calling 800-442-6622. |
|
|
6 |
PROBLEM: |
|
|
LED
indicator blinks when faucet is in use. |
|
|
CAUSES: |
|
|
A) Battery
low |
|
|
SOLUTION: |
|
A) Replace
battery. Order part # 80775 from Equiparts by calling 800-442-6622. |
|
|
7 |
PROBLEM: |
|
|
The
water temperature is too hot or too cold on a faucet
connected to hot and cold supply lines. |
|
|
CAUSES: |
|
|
A) Supply
stops are not adjusted properly. |
|
B) For
models with integral mixing valve - mixing valve is set improperly
for the water temperature desired. |
|
|
SOLUTION: |
|
A) Adjust
supply stops |
|
B) Rotate
mixing valve handle clockwise to decrease water temperature
or counterclockwise to increase water temperature. OR, install
thermostatic mixing vale, part # 54621. To order,call Equiparts
at 800-442-6622. |
|
|