SLOAN ELECTRONIC FAUCET REPAIR PARTS BREAKDOWN
EBF-750
Sloan EBF-750 faucet repair parts
1A
# 81317
Faucet/Sensor Assembly with standard Gooseneck Spout (EBF-750)
1B
# 80748
Faucet/Sensor Assembly with Surgical Bend Gooseneck Spout (EBF-750-S)
2
# 80749
Spray Head w/Key - (female 0.5 gpm)
# 55670
Aerator Spray Head w/Key (female 2.2 gpm)
# 54677
Laminar Flow Spray Head (female 2.2 gpm )
2B
# 80750
Shower Spray Head Assembly (2.2 gpm)
3
# 80751
Adapter for Spray Heads
4
# 54693
Replacement Key only for ETF-1021-A 0.5 gpm Spray Head and aerator spray head
5
# 80325
Spout Mounting Kit includes Rubber Gasket, Flat Washer, Lock Washer, Mounting Nut, and ETF-530 Union Compression Fitting.
6
# 80752
3/8" x 3/8" Union Compression Fitting - Female
7
# 54325
Control Module Assembly includes  Base Enclosure, Cover Enclosure, two Gaskets, Solenoid Body, Solenoid Enclosure, Solenoid Filter Cap, and Battery Stop.
8A
# 80753
Single Solenoid Supply Kit includes two Compression Nuts, two Compression Sleeves, and Screwdriver
8B
# 54682
3/8" Tee Compression Fitting
9
# 54686
Mounting Hardware for Control Module Assembly - Includes four Anchor Nuts, four Toggle Nuts, four Mounting Screws for Base Plate,  four Flat Washers, four Anchors, and four Metal Screws.
10
# 08218 Back Check
11
# 52114
Optional 8" Centerset Trim Plate Kit
12 # 54676 Optional 4" Centerset Trim Plate Kit
- # 80377 Sensor Replacement Kit includes Sensor Housing and Cable Assembly
- # 80754 Solenoid Replacement Kit includes Solenoid Body, Solenoid Enclosure, and Solenoid Filter Cap.
- # 08578 Solenoid Filter Replacement Kit includes Filter Screen Assembly and O-Ring
- # 80755 Repair Kit includes for EBF-60 Control Module Assembly includes EBF-61 Battery Holder Assembly and EBF-159 Battery Gasket
- # 80756 Control Module Replacement Gaskets (two required)
MAINTENANCE GUIDE FOR THE EBF-750 FAUCET
 
1
PROBLEM:
Sensor troubleshooting LED does not function (red indicator light does not flash during set-up procedure.)
CAUSE:
A) No battery power is being supplied to Sensor
B) Insufficient battery power is being supplied to Sensor
C) Sensor Cable is not properly inserted
D) Sensor Range is set at minimum distance
E) Control Module assembly is defective
SOLUTIONS:
A) Ensure that the batteries are installed properly. Check that the orientation of each battery matches the positive and negative symbols shown on the bottom of the battery compartment. Reinsert the Battery Compartment into the Control Module.

B) One or more of the batteries is "dead." To ensure proper operation, replace with four C-size batteries
( order four # 32739 batteries from Equiparts by calling 800-442-6622.) Check that the orientation of each battery matches the positive and negative symbols shown on the bottom of the battery compartment. Reinsert the Battery Compartment into the Control Module.

C) Disconnect and reconnect Sensor Cable to the Control Module.
D) Increase Sensor range. Use a small phillips screwdriver to turn the potentiometer screw (white screw in a blue base) clockwise.
E) Replace EBF-60-A Control Module assembly by ordering part # 54325 from Equiparts. Call 800-442-6622 to order.
2
PROBLEM:
Faucet does not deliver any water when Sensor is activated.
INDICATOR:
A) Solenoid valve produces an audible "click."
CAUSE:
A) Water supply valve is closed
SOLUTION:
A) Open the supply stop.
INDICATOR:
B) Solenoid valve does NOT produce an audible "click."
CAUSE:
B) Solenoid lead is not properly connected to the Control Module
SOLUTION:
B) Disconnect and reconnect Solenoid lead to the Control Module
CAUSE:
C) Batteries are not installed properly.
SOLUTION:
C) Check that the orientation of each battery matches the positive and negative symbols shown on the bottom of the battery compartment. Reinsert the battery compartment into the control module. The troubleshooting LED should flash red when a user is detected
CAUSE:
D) Solenoid needs replaced
SOLUTION:
D) Order part # 54335 from Equiparts. To order, call 800-442-6622.

3
PROBLEM:
Faucet delivers only a slow flow or dribble when sensor is activated.
CAUSES:
A) Water supply valve is partially closed.
B) Solenoid Filter is clogged.
C) Aerator or Spray Head is clogged.
D) Aerator needs replaced.
SOLUTIONS:
A) Completely open the Supply Stop.
B) Remove, clean, and reinsert. Replace (EBF-1004-A) Solenoid Filter Kit if necessary by ordering part # 08578 from Equiparts. Call 800-442-6622 to order.
C) Remove, clean, and reinsert.
D) Call Equiparts at 800-442-6622 to order part # 59857.

4
PROBLEM:
Faucet does not stop delivering water or continues to drip after user is no longer detected (automatic shut-off fails even when batteries are removed.)
CAUSE:
A) Solenoid Valve has been connected backwards.
  B) Solenoid Valve is dirty.
  C) Solenoid Valve Module is defective.
 
SOLUTIONS:
A) Disassemble Solenoid Valve compression fittings at the inlet and outlet positions. Water should flow from inlet through the Solenoid Valve to outlet according to the direction shown by the arrow on the side of the Solenoid Valve. Reconnect the compression fittings in the correct orientation.
B) Back flush by reversing water flow (opposite to the direction shown by the arrow on the side of the Solenoid Valve) through the Solenoid Valve. Reconnect the compression fittings in the correct orientation. Activate faucet.
C) Replace (EBF-62-A) Solenoid Valve Module by ordering part # 80754 from Equiparts. Call 800-442-6622 to order.

5
PROBLEM:
The water temperature is too hot or too cold on a faucet connected to hot and cold supply lines with two Back Checks.
CAUSES:
A) Supply Stops are not adjusted properly.
B) One Back Check is installed backwards.
SOLUTIONS:
A) Adjust Supply Stops
B) Reinstall Back Check
NOTE: For some systems, a thermostatic mixing valve may be required. Order part # 54621 from Equiparts. Call 800-442-6622 to order.